Humidistats for DIN rail mounting
-
DESCRIPTION
General features0
Humidistat for humidification or dehumidification systems with a single outlet.
Configurable parameters:
- dehumidification or humidification function by assigning positive or negative sign to the differential respectively
- minimum or maximum setpoint limits
- ON or OFF status of the output in the event of a defective probe
Operating temperature -10 to 50°C.
Degree of protection IP40.
Accessories:
LS160A
RH% probe,
scale range from 0 to 100 %RHElectric featuresOutput on single-pole relay in deviation.
Contact rating 12(3.6)A 240Vac.
Power consumption 3W. -
ADVANTAGES
0
Humidistat for humidification or dehumidification systems with a single outlet.
Advantages -
TECHNICAL SPECIFICATION
Code Sensor Num outputs Power supply Measuring range RH% Resolution RH% Measuring accuracy (0-100 RH%) Protection degree L23EM1B probe (LS160A) 1 230 Vac 0 - 100 1 <± 0.7 IP40 back panel -
HOMOLOGATION AND INSTALLATION
Homologation
Compliant with EN60730-1, EN60730-2-9, EN55022 (CLASS B), EN50082-1.
Installation and useDIN rail mounting
Type of control: can operate in ON/OFF or PID mode.
ON/OFF control: in ON/OFF mode the output is ON or OFF depending on the input humidity, setpoint (1SP) and hysteresis value (1HY).
The hysteresis indicates the amplitude of the deviation of the setpoint humidity to reactivate the output.
PID control: in PID mode the output is ON for a fraction of cycle time 1CT.
The cycle time characterises the dynamics of the system to be controlled and influences the accuracy of the control.
Proportional control.
Integrative proportional control. - TECHNICAL LITERATURE
-
FAQS